250-400 CFM Vertical Conditioner

PRECISE CONTROL IN A COMPACT PACKAGE

Request a Quote

This unit is specifically designed to provide 250-400 CFM of conditioned air to small rooms and reach-in chambers.

This unit is a great choice if you do not have ceiling space above to house a conditioner. This vertical unit attaches directly to the wall of the room to minimize floor space required.

The 250-400 CFM unit is one of our smaller conditioners and is designed to easily connect to the conditioned space. This unit does not require compressed air or ultra pure water (tap water is generally fine). The interior and exterior are constructed of corrosion-resistant stainless steel. Low watt-density heaters also contribute to the unit’s durability. Various safety devices are also included.

The conditioner is controlled by Parameter’s Smart Pad, a user-friendly system that provides optimum accuracy and control. The Smart Pad is equipped with direct readings for both temperature and humidity. It also features 60 segment programming for automatic cycling. High-low or deviation alarms and serial communications port (with software) are standard.

To download product specifications pdf, click here.

 

Description

The 250-400 CFM Vertical Conditioner is designed to produce very precise humidity and temperature control for small rooms and reach-in chambers. This vertical unit attaches directly to the wall of the room to minimize floor space required and is a great choice if you do not have ceiling space above to house a conditioner.

Features and benefits of the 250-400 CFM Vertical Conditioner, series 9224-31E0, include:
Precise temperature and humidity control
High grade temperature compensated humidity sensor
Stainless steel construction
High-low or deviation alarms
Compact package
Consistent and accurate results
Confidence in the measured condition
Durability
Security and safety
Easy application


SYSTEM IS DESIGNED FOR CONNECTION TO:

10 or 25 cubic foot Parameter reach-in chamber.
Existing reach-in chambers.
Walk-in rooms (existing or provided by Parameter).

RH Variables

RH Variables Parameter Competition
Total ± 2.5% ± 6.0%
Control Constancy ± 0.5% ± 2.0%
Chamber Uniformity ± 1.0% ± 2.0%
Sensor Accuracy ± 1.0% ± 2.0%

Specifications

Relative Humidity Control: ±0.5%
Relative Humidity Uniformity: ±0.5%
Relative Humidity Accuracy: ±1.0% 
Relative Humidity Range: 20 to 93% 
Temperature Control: ±0.2°C 
Temperature Uniformity: ±0.2°C
Temperature Accuracy: ±0.2°C 
Temperature Range: 5 to 50°C

Utilities

Domestic: 208/230V, 1-Phase, 60 Hz, 12.21 FLA, 9.42 RLA
International: 230V, 1-Phase, 50Hz, 12 FLA, 9 RLA
Water: 3 gallon per day maximum 
Condensate Drain: 3 gallon per day maximum

Weight & Dimensions

WEIGHT

640 lbs.


SHIPPING WEIGHT

750 lbs.


DIMENSIONS

28”w x 15”d x 77”h

Quote Request